Galaxy 5500

20/30/40/60/80/100/120 kVA

The Galaxy 5500 can be equipped with an isolation transformer, fully integrated to the UPS unit depending on the customer’s galvanic isolation need (output or input). Integrating the transformer directly to the UPS unit saves footprint and provides all the benefits of galvanic isolation including a very robust buffer between the utility and the critical load.


Download Brochure


SKU: 82D-1-1-1 Category:

Description

Normal AC supply input
Input voltage250 V to 470 V, three-phase
Normal and bypass AC inputsseparate, common in option
Frequency45 – 66 Hz
Input power factor> 0.99
THDI< 3% full load
Bypass AC Input
Input voltage range(380 V, 400 V, 415 V) +/- 10%
Frequency50/60 Hz +/- 10%
Output
Phase to phase output voltage380/400/415 V, three-phase + neutral
Load power factor0.9
Output frequency50/60 Hz +/- 0.1%
Overload capacity utility operation125% for 10 minutes; 150% for 60 seconds
Output voltage regulation+/- 1%
Voltage distortion (THD)< 2% phase-to-phase and phase-to-neutral for nonlinear loads
Output voltage tolerance+1% static, +/- 2% at 100% load step
Overall efficiency
Efficiency at full load AC/AC at 100% loadUp to 94%
ECO modeup to 97%
Communication and management
Control panelMultifunction LCD, status, and control console